TVJ_img_04psd.png
VAV terminal unit Type TVJ/400×200/Easy

Easyregler-Compactregler_img_01_2020_01_DE__3_psd.psd.link
Easy controller, Compact controller

Easy controller, Compact controller

VRU-D3-M-B_LM24A-VST_img_01psd.png

Universal controller (VARYCONTROL)

TU-ELAB-Regler_img_01_2020_01_DE__4_psd.psd.link

TROX UNIVERSAL controller,

TROX LABCONTROL controller

TVJ_img_02psd.psd.link
VAV terminal unit, variant TVJ-D

Construction with acoustic cladding

TVJ_img_04psd.png
Easyregler-Compactregler_img_01_2020_01_DE__3_psd.psd.link
VRU-D3-M-B_LM24A-VST_img_01psd.png
TU-ELAB-Regler_img_01_2020_01_DE__4_psd.psd.link
TVJ_img_02psd.psd.link

TVJ  

FOR NORMAL AND HIGH VOLUME FLOW RATE RANGES


  • Rectangular air terminal units for standard applications in supply air or extract air systems with variable volume flow rates
  • Suitable for volume flow rate ranges up to approx. 62,000 m³/h or 17,000 l/s
  • Suitable for the control of volume flow rate, room pressure or duct pressure
  • Electronic control components for different applications (Easy, Compact, Universal, and LABCONTROL)
  • High control accuracy
  • Closed blade air leakage to EN 1751, Class 1 (B + H ≥ 600 mm)
  • Casing air leakage to EN 1751, class B


Optional equipment and accessories

  • Acoustic cladding for the reduction of case-radiated noise
  • Secondary silencer Type TX for the reduction of air-regenerated noise
  • Hot water heat exchanger Type WT for reheating the airflow

 

 


General Information

Application

  • Rectangular VAV terminal units for use in ventilation and air conditioning systems
  • For controlling, restricting, or shutting off supply and extract
  • air flows
  • Closed-loop volume flow control using an external power supply
  • For variable or constant volume flow systems
  • Shut-off by means of switching (equipment supplied by others)
  • Can also be used for duct or room pressure control with suitable control components


Special characteristics

  • Integral effective pressure sensor with 3 mm measuring holes (resistant to dust and pollution)
  • Factory set-up or programming and aerodynamic function testing
  • Parameters can also later be set on the control component. Depending on the control component, an additional adjustment device may be necessary

Nominal sizes

  • 39 nominal sizes from 200 × 100 to 1000 × 1000
  • Not all attachments with fast-running actuators may be available or suitable for all sizes of terminal units.


Variants

  • TVJ: VAV terminal unit
  • TVJ-D: VAV terminal unit with acoustic cladding
  • Units with acoustic cladding and/or secondary silencer Type TX for demanding acoustic requirements
  • Acoustic cladding cannot be retrofitted


Construction

  • Galvanised sheet steel
  • P1: Powder-coated, silver grey (RAL 7001)


Parts and characteristics

  • Ready-to-commission unit which consists of mechanical parts and control components.
  • Averaging effective pressure sensor for volume flow rate measurement
  • Damper blades
  • Factory mounted control components complete with wiring and tubing
  • Aerodynamic functional testing on a special test rig before shipping of each unit
  • Set-up data is given on a label or volume flow rate scale affixed to the unit
  • High volume flow rate control accuracy


Attachments

  • EASY controller: compact unit consisting of controller with potentiometers, effective pressure transducer and actuator
  • Compact controller: compact unit consisting of controller with potentiometers, effective pressure transducer and actuator
  • Universal controller: controller, effective pressure transducer, and actuators for special applications
  • LABCONTROL: Control components for air management systems


Useful additions

  • Secondary silencer Type TX for demanding acoustic requirements
  • Heat exchanger Type WT


Construction features

  • Rectangular casing
  • Flanges on both ends, suitable for duct connection
  • Opposed blade action, blades connected by internal gears at both ends
  • Position of the damper blade indicated externally at shaft extension
  • Bearings with ring seals


Material and surfaces

  • Galvanised sheet steel construction
  • Casing made of galvanised sheet steel
  • Shafts made of galvanised steel
  • Damper blades and effective pressure sensor made of aluminium
  • Gears made of anti-static plastic (ABS), temperature resistant to 50 °C
  • Plastic plain bearings


Powder-coated construction (P1)

  • Casing made of galvanised sheet steel, powder-coated


Variant with acoustic cladding (-D)

  • Acoustic cladding made of galvanised sheet steel
  • Rubber seal for the insulation of structure-borne noise
  • Lining is mineral wool


Mineral wool

  • To EN 13501, fire rating Class A1, non-combustible
  • RAL quality mark RAL-GZ 388
  • Non-hazardous to health thanks to being highly biosoluble in accordance with the Ordinance on Hazardous Substances and Note Q of the European Directive (EC) No. 1272/2008


Standards and guidelines

Casing leakage

  • EN 1751, Class B

Closed blade air leakage

  • EN 1751, Class 1 (B + H ≥ 600 mm)


Maintenance

  • Maintenance-free as construction and materials are not subject to wear

Technical information

  • Function
  • TECHNICAL DATA
  • SPECIFICATION TEXT
  • ORDER CODE
Schematic illustration of the TVJ TVJ_gc_05ai.png

① Effective pressure sensor

② Damper blade

③ Gears

④ Control components, e.g. an Easy controller


The VAV terminal unit is fitted with an effective pressure sensor for measuring the volume flow rate. The control components (attachments) include an effective pressure transducer that transforms the effective pressure into an electric signal, a controller, and an actuator; the control functions can be achieved with an Easy controller or with a Compact controller or with individual components (Universal or LABCONTROL). For most applications, the setpoint value comes from a room temperature controller. The controller compares the actual value with the setpoint value and alters the control signal of the actuator if there is a difference between the two values.

 


Nominal sizes

200 × 100 – 1000 × 1000 mm

Volume flow rate range

42 – 17,223 l/s or 149 – 62,005 m³/h

Volume flow rate control range (unit with dynamic effective

pressure measurement)

approx. 20 to 100 % of the nominal volume flow rate

Minimum differential pressure

Up to 109 Pa (without secondary silencer)

Maximum differential pressure

1000 Pa

Operating temperature

10 to 50 °C

This specification text describes the general properties of the product. Texts for variants can be generated with our Easy Product Finder design program.


Specification text

Rectangular VAV terminal units for variable and constant air volume systems, suitable for supply or extract air, available in 39 nominal sizes. High volume flow rate control accuracy. Ready-to-commission unit which consists of the mechanical parts and the electronic control components. Each unit contains an averaging effective pressure sensor for volume flow rate measurement and damper blades. Factory mounted control components complete with wiring and tubing. Position of the damper blades indicated externally at the shaft extension. The damper blade is factory set to open position, which allows a ventilation airflow even without control; this does not apply to variants with defined safe position NC (normally closed).

Special features

  • Integral effective pressure sensor with 3 mm measuring holes (resistant to dust and pollution)
  • Factory set-up or programming and aerodynamic function testing
  • Parameters can also later be set on the control component. Depending on the control component, an additional adjustment device may be necessary


Materials and surfaces

  • Casing made of galvanised sheet steel
  • Shafts made of galvanised steel
  • Damper blades and differential pressure sensor made of aluminium
  • Gears made of anti-static plastic (ABS), resistant to temperatures up to 50 °C
  • Plastic plain bearings


Connection type

  • Flanges on both ends, suitable for duct connection


Technical data

  • Nominal sizes: 200 × 100 to 1000 × 1000 mm
  • Volume flow rate range: 42 – 10454 l/s or 149 – 37635 m³/h
  • Minimum differential pressure: up to 109 Pa (without secondary silencer)
  • Maximum differential pressure: 1000 Pa
  • Casing air leakage to EN 1751, class B
  • Closed blade air leakage to EN 1751, Class 1 (B + H ≥ 600 mm)


Equivalence criteria

  • Acoustic data to ÖNORM EN ISO 5135:1999
  • Setting of the volume flow rates without adjustment device using qvmin and qvmax potentiometers
  • Electrical connections with screw terminals, no junction box required
  • Aerodynamic functional testing of each volume flow controller on a test rig at the factory; the test result is given on a sticker on the controller


Specification text attachment

Variable volume flow control with electronic Easy controller for applying a reference value and capturing an actual value to be integrated with the central BMS.

  • Supply voltage 24 V AC/DC
  • Signal voltages 0 – 10 V DC
  • Possible override controls with external switches using volt free contacts: CLOSE, OPEN, qᵥmin and qᵥmax
  • Potentiometers with percentage scales to set the volume flow rates qᵥmin and qᵥmax without an adjustment device
  • The actual value signal relates to the nominal volume flow rate such that commissioning and subsequent adjustment are simplified
  • Volume flow rate control range: approx. 20 – 100 % of the nominal volume flow rate
  • Clearly visible external indicator light for signalling the functions: Set, not set, and power failure
  • Electrical connections with screw terminals
  • Double terminals for looping the supply voltage, i.e. for the simple connection of voltage transmission to the next controller


Sizing data

  • qᵥ _______________________ [m³/h]
  • Δpst _______________________[Pa]

Air-regenerated noise

  • LPA _______________________[dB(A)]

Case-radiated noise

  • LPA _______________________[dB(A)]


Life cycle assessment

A life cycle assessment is available for the product type in the form of an environmental product declaration (EPD), which has been checked and published by a programme holder.


Order code for volume flow control (with Easy attachment)
TVJD / 900 × 300 / Easy
||||
1245

1 Type
TVJ VAV terminal unit

2 Acoustic cladding
No entry: none
D with acoustic cladding

4 Nominal size [mm]
B × H

5 Attachments (control component)

Easy Volume flow controller, dynamic, analogue interface, setting of qᵥmin and qᵥmax with potentiometers (provided on site)



Order example: TVJ-D/500×400/Easy
Acoustic claddingWith
MaterialGalvanised sheet steel
Nominal size500 × 400 mm
Attachments (control components)Easy controller; volume flow controller, dynamic, analogue interface,
setting of qvmin and qvmax with potentiometers



Downloads

informazioni di prodotto

certificati

manuali d'uso

Referenze

production {"X-Frame-Options"=>"SAMEORIGIN", "X-XSS-Protection"=>"1; mode=block", "X-Content-Type-Options"=>"nosniff", "X-Download-Options"=>"noopen", "X-Permitted-Cross-Domain-Policies"=>"none", "Referrer-Policy"=>"strict-origin-when-cross-origin", "Strict-Transport-Security"=>"max-age=31536000; includeSubDomains", "Content-Type"=>"text/html; charset=utf-8"}

Condividi pagina

Consiglia questa pagina

Consiglia questa pagina inviando un link via e-mail.

I campi contrassegnati con (*) sono obbligatori.

Condividi pagina

Grazie per la tua condivisione!

La tua segnalazione è stata inviata e dovrebbe arrivare a breve.


Contatti

Siamo qui per te

Specifichi il suo messaggio ed il tipo di richiesta
Tel.: +41 26 425 59 00 | Fax: +41 55 250 73 10 | Fax Fribourg: +41 26 425 59 01

I campi contrassegnati con (*) sono obbligatori.

Contatti

Grazie per il tuo messaggio!

Il tuo messaggio è stato inviato e sarà processato a breve.
Il nostro dipartimento per la gestione delle richieste ti contatterà appena possibile.
Per domande di carattere generale riguardanti i nostri prodotti o servizi, è possibile contattare:
Tel.: +41 26 425 59 00 | Fax: +41 55 250 73 10 | Fax Fribourg: +41 26 425 59 01

Contatti

Siamo qui per te

Specifichi il suo messaggio ed il tipo di richiesta
Tel.: +41 26 425 59 00 | Fax: +41 55 250 73 10 | Fax Fribourg: +41 26 425 59 01

Attachment (max. 10MB)

I campi contrassegnati con (*) sono obbligatori.

Contatti

Grazie per il tuo messaggio!

Il tuo messaggio è stato inviato e sarà processato a breve.
Il nostro dipartimento per la gestione delle richieste ti contatterà appena possibile.
Per domande di carattere generale riguardanti i nostri prodotti o servizi, è possibile contattare:
Tel.: +41 26 425 59 00 | Fax: +41 55 250 73 10 | Fax Fribourg: +41 26 425 59 01