Steel door with inspection window, pressure relief valve and cylinder rim lock(Profile cylinder on the opening side, cylinder rim lock on the closing side)
Application
Special characteristics
Nominal sizes
ST (single leaf)
ST-D (double leaf)
Any combination of B × H
Variants
Parts and characteristics
Attachments
Construction features
Materials and surfaces
Mineral wool
Maintenance
Functional description
Low-leakage steel doors are low-leakage separating elements for rooms or other enclosures.
When the door is being closed, i.e. when the double locking levers are being turned, the perimeter seal is fully pressed against the frame. As a consequence, the air leakage rate is extremely low even in case of high differential pressures.
Nominal sizes (single leaf) | 400 × 800 to 1100 × 2115 mm |
Nominal sizes (double leaf) | 1080 × 800 to 2280 × 2115 mm |
Maximum pressure on the opening side | 1000 Pa (reinforced construction: 2000 Pa) |
Weighted sound reduction index (with sound absorbing infill) | Single leaf door 43 – 46 dB, double leaf door 44 – 47 dB, doors on both sides of the wall opening 58 – 61 dB |
Weighted sound reduction index
ST-X, ST-X-V | 26 | 38 | 44 | 46 | 46 |
ST-D-X, ST-D-X-V | 28 | 41 | 45 | 49 | 46 |
2 × ST-X, ST-X-V, doors on both sides of the wall opening | 48 | 52 | 59 | 62 | 65 |
Low-leakage steel doors as separating elements for walk-in plant rooms, storage rooms, air handling units, filter chambers, or enclosures for machinery or electrical equipment.
Ready-to-install component that consists of a door leaf with double lever locking devices, absorption material, seal and hinges, and a frame.
Air leakage rate on the opening side is approx. 0.6 l/s or 2 m³/h at 1000 Pa (single leaf door).
Special characteristics
Materials and surfaces
Mineral wool
Technical data
This specification text describes the general properties of the product. Texts for variants can be generated with our Easy Product Finder design programme.
Order example: ST–R/800×1800/21/Z06
Hinge | Right side |
Sound insulating lining | Without |
Construction of door | Standard construction |
Nominal size | 800 × 1800 mm |
Door frame | Angle section, without fixing tabs |
Attachments | Standard construction with inspection window and cylinder rim lock |
Surface | Standard construction |
Order example: ST–D/1680×1800/21/Z06
Number of door leaves | Double leaf low-leakage steel door |
Sound insulating lining | Without |
Construction of door | Standard construction |
Nominal size | 1680 × 1800 mm |
Door frame | Angle section, without fixing tabs |
Attachments | Standard construction with inspection window and cylinder rim lock |
Surface | Standard construction |
ST
Variant
Parts and characteristics
Construction features
ST-V
Variant
Parts and characteristics
Construction features
ST-X
Variant
Parts and characteristics
Construction features
ST-X-V
Variant
Parts and characteristics
Construction features
ST-D
Variant
Parts and characteristics
Construction features
ST-D-V
Variant
Parts and characteristics
Construction features
ST-D-X
Variant
Parts and characteristics
Construction features
ST-D-X-V
Variant
Parts and characteristics
Construction features
ST, width, dimensions
<500 | B + 30 |
500 | 530 |
600 | 630 |
800 | 830 |
940 | 970 |
ST, height, dimensions
<1500 | H + 30 | 249.5 |
1500 | 1530 | 349.5 |
1600 | 1630 | 349.5 |
1800 | 1830 | 349.5 |
1940 | 1970 | 349.5 |
ST-D, width, dimensions
B < 1080 | (B – 20) ∕ 2 | B + 30 |
1080 | 530 | 1110 |
1280 | 630 | 1310 |
1680 | 830 | 1710 |
1960 | 970 | 1990 |
ST, ST-V, weights
1500 | 33 | 40 | 53 | 62 |
1600 | 34 | 41 | 54 | 64 |
1800 | 35 | 42 | 56 | 66 |
1940 | 36 | 43 | 57 | 67 |
ST-X, ST-X-V, weights
1500 | 36 | 43 | 58 | 68 |
1600 | 37 | 44 | 59 | 70 |
1800 | 38 | 46 | 61 | 71 |
1940 | 39 | 46 | 62 | 73 |
ST-D, ST-D-V, weights
1500 | 66 | 78 | 102 | 120 |
1600 | 68 | 81 | 106 | 123 |
1800 | 70 | 83 | 109 | 127 |
1940 | 72 | 86 | 113 | 131 |
ST-D-X, ST-D-X-V, weights
1500 | 72 | 86 | 113 | 131 |
1600 | 75 | 88 | 116 | 135 |
1800 | 77 | 91 | 119 | 139 |
1940 | 80 | 95 | 124 | 145 |
Installation and commissioning
Angle section frame, no. of fixing tabs or flange holes
1500 | 6 | 8 |
1600 | 6 | 8 |
1800 | 8 | 10 |
1940 | 8 | 10 |
U-channel door frame, dimensions
13 | 115 |
15 | 240 |
Condividi pagina
Consiglia questa pagina
Consiglia questa pagina inviando un link via e-mail.
Condividi pagina
Grazie per la tua condivisione!
La tua segnalazione è stata inviata e dovrebbe arrivare a breve.
Contatti
Siamo qui per te
Specifichi il suo messaggio ed il tipo di richiesta
Tel.: +41 26 425 59 00 | Fax: +41 55 250 73 10 | Fax Fribourg: +41 26 425 59 01
Contatti
Grazie per il tuo messaggio!
Il tuo messaggio è stato inviato e sarà processato a breve.
Il nostro dipartimento per la gestione delle richieste ti contatterà appena possibile.
Per domande di carattere generale riguardanti i nostri prodotti o servizi, è possibile contattare:
Tel.: +41 26 425 59 00 | Fax: +41 55 250 73 10 | Fax Fribourg: +41 26 425 59 01
Contatti
Siamo qui per te
Specifichi il suo messaggio ed il tipo di richiesta
Tel.: +41 26 425 59 00 | Fax: +41 55 250 73 10 | Fax Fribourg: +41 26 425 59 01
Contatti
Grazie per il tuo messaggio!
Il tuo messaggio è stato inviato e sarà processato a breve.
Il nostro dipartimento per la gestione delle richieste ti contatterà appena possibile.
Per domande di carattere generale riguardanti i nostri prodotti o servizi, è possibile contattare:
Tel.: +41 26 425 59 00 | Fax: +41 55 250 73 10 | Fax Fribourg: +41 26 425 59 01