Application
Special characteristics
Parts and characteristics
Construction features
Functional description
The expansion module EM-BAC-MOD is used to integrate EASYLAB controllers Type TCU3 or EASYLAB adapter modules Type TAM into a BACnet (MS/TP) network and in this way connect them to the central BMS.
The BACnet or Modbus interface supports the EASYLAB room operating mode concept. It is possible to set operating mode defaults in order to control different volume flow rates for daytime and night-time operation; it is also possible to increase or reduce the air change rate (volume flow rate setpoint change), e.g. to influence the room temperature.
Using the BACnet or Modbus interface, an individual alarm management system can be set up by consolidating configurable EASYLAB alarms. The interface also enables the transfer of actual operating values such as volume flow rates and damper blade position for a controller or for all controllers in a room.
Supply voltage | 5 V DC from controller or adapter module |
Communication interface | EIA-485 standard |
Protocol | BACnet MS/TP standard rev. 12 or Modbus RTU |
Data transmission speeds | BACnet: 9600, 19200, 38400, 76800 Bd, Modbus: 9600, 19200, 38400, 57600 Bd |
Parity checks for data transmission security | None, odd, even |
Configurable network addresses | 01 … 99 |
Operating temperature | 0 – 50 °C |
IEC protection class | III (protective extra-low voltage) |
Protection level | IP 20 |
EC conformity | EMC according to 2004/108/EC |
Dimensions (B × H × T) | 78 × 65 ×100 mm |
Expansion module to supplement an EASYLAB base component (controller TCU3 or adapter module TAM) with a BACnet or Modbus interface to link rooms or individual volume flow controllers to the central BMS.
The expansion module includes an interface for EIA-485 networks that can be used for BACnet MS/TP or Modbus RTU (switching), a switch to enter communication parameters, a connection to update the firmware, and indicator lights.
Special characteristics
Technical data
Data points for a single controller
Additional data points for a fume cupboard controller
Data points for an EASYLAB room
Single controller
Interface for one EASYLAB controller
Data points for a single controller
Additional data points for a fume cupboard controller
EASYLAB room
Interface for one EASYLAB room
Data points for an EASYLAB room controller
BACnet interface
Application
The expansion module EM-BAC-MOD supports the following interface functions on an EASYLAB controller TCU3 or an adapter module TAM if the BACnet protocol has been selected:
BACnet PICS (Protocol Implementation Conformance Statement) – Overview
Date | 2014-01-21 |
Vendor name | TROX GmbH |
Vendor identifier | 329 |
Product name | EM-BAC-MOD |
Model no. | M536HD7 |
Application | 4.0 |
Firmware Revison | 4.0 |
BACnet Protocol Revision | 12 |
Standarised Device Profile | BACnet Application Specific Controller (B-ASC) |
Segmentation Capability | No |
Data Link Layer Options | MS/TP master (Clause 9), Baudrates 9600, 19200, 38400, 76800 |
Device Address Binding | No |
Network Security Options | Non-secure Device - is capable of operating without BACnet Network Security |
Character Sets Supported | ISO 10646 (UTF-8) |
Configuration switches
DIP Switch 1 | OFF | ON | ||
Controller | EASYLAB TCU3 | Other | ||
DIP Switch 2 | OFF | ON | OFF | ON |
DIP Switch 3 | OFF | OFF | ON | ON |
Baud rate | 9600 | 19200 | 38400 | 76800 |
BIBBS - BACnet Interoperability Building Blocks Supported
Data Sharing-ReadProperty-B | DS-RP-B |
Data Sharing-WriteProperty-B | DS-WP-B |
Data Sharing-COV-Unsolicited-B | DS-COVU-B |
Device Management-Dynamic Device Binding-B | DM-DDB-B |
Device Management-Dynamic Object Binding-B | DM-DOB-B |
Device Management-Device Communication Control-B | DM-DCC-B |
Device Management-ReinitialiseDevice-B | DM-RD-B |
DeviceObject
Object identifier | Device instance; default instance = 32900 + set network address | WR, RD; E |
Object name | Default="EM-BACnet"; project-specific description can be entered, 62 characters max. | WR, RD; E |
Object type | Device (8) | RD |
System_Status | OPERATIONAL (0) | RD |
Vendor_Name | "TROX GmbH" | RD |
Vendor_Identifier | 329 | RD |
Model_Name | "EM-BAC-MOD" | RD |
Description | Default = “EASYLAB”; description can be entered, 126 characters max. | WR, RD; E |
Location | Default = ""; description can be entered, 62 characters max. | WR, RD; E |
Firmware_Revision | “4.0” (EASYLAB) | RD |
Application_Software_Version | “4.0” (EASYLAB) | RD |
Protocol_Version | 1 | RD |
Protocol_Revision | 12 | RD |
Protocol Services Supported | Who-is, Who-has, Read-Property, Write-Property, Device-communication-control, Reinitialize-device | RD |
Protocol_Object_Types_Supported | DEVICE, ANALOG_VALUE, BINARY_VALUE, MULTISTATE_VALUE | RD |
Object_List | EASYLAB: device, analog-value 1…36, binary-value 1…30, multistate-value 1…8 | RD |
Max_ADPU_Length_Accepted | 480 | RD |
Segmentation_Supported | NO_SEGMENTATION (3) | RD |
APDU_Timeout | 10000 | RD |
Number_Of_APDU_Retries | 3 | RD |
Device_Address_Binding | – | RD |
Database_Revision | 0 | RD |
Description | Controller Type “EASYLAB” | RD |
Max_Master | Default 127 | WR, RD; E |
Max_Info_Frames | Default 1 | WR, RD; E |
Multistate Value Objects
1 | COVU mode | x | x | x | x | x | x | WR, RD |
2 | Mode | x1 | x | x | WR, RD | |||
3 | ModeAct | x | x | x | x | RD | ||
4 | RoomModeAct | x | x | RD | ||||
5 | SwitchPos | x | RD | |||||
6 | Sunblind | x | x | WR, RD | ||||
7 | SC_SetLockHighPrio | WR, RD | ||||||
8 | SC_GetLockHighPrio | RD |
1 only for individually selected operating mode (stand-alone operation)
FH: Fume cupboard controller
RR: Room controller for supply air or extract air (RS, RE, PC)
RR RMF: Room controller with active room management function
EC, SC: Single controller for supply air or extract air (EC, SC)
TAM: Adapter module
TAM RMF: Adapter module with active room management function
Analogue Value Objects
1 | VolflowSet | l/s (87) | x | x | x | x | x | RD | |
2 | VolflowAct | l/s (87) | x | x | x | x | x | RD | |
3 | VolTotalExh | l/s (87) | x | x | x | x | x | x | RD |
4 | VolTotalSup | l/s (87) | x | x | x | x | x | x | RD |
5 | PressSet | Pa (53) | x | x | RD | ||||
6 | PressAct | Pa (53) | x | x | RD | ||||
7 | VelocitySet | m/s (74) | x | RD | |||||
8 | VelocityAct | m/s (74) | x | RD | |||||
9 | WireSensorPos | percent (98) | x | RD | |||||
10 | DampPos | percent (98) | x | x | x | x | RD | ||
11 | DampPosMax_FH | percent (98) | x | x | x | x | x | x | RD |
12 | DampPosMin_FH | percent (98) | x | x | x | x | x | x | RD |
13 | DampPosMax_RE | percent (98) | x | x | x | x | x | x | RD |
14 | DampPosMin_RE | percent (98) | x | x | x | x | x | x | RD |
15 | DampPosMax_TE | percent (98) | x | x | x | x | x | x | RD |
16 | DampPosMin_TE | percent (98) | x | x | x | x | x | x | RD |
17 | DampPosMax_RS | percent (98) | x | x | x | x | x | x | RD |
18 | DampPosMin_RS | percent (98) | x | x | x | x | x | x | RD |
19 | VolOffset_T | percent (98) | x | x | WR, RD | ||||
20 | VolOffset_P | percent (98) | x | x | WR, RD | ||||
21 | SystemDevices | no units (95) | x | x | x | x | x | x | RD |
22 | VolflowExh | l/s (87) | x | x | x | x | x | WR, RD | |
23 | VolflowSup | l/s (87) | x | x | x | x | x | WR, RD | |
24 | SC_SetPos | percent (98) | WR, RD | ||||||
25 | SC_GetPos | percent (98) | RD | ||||||
26 | DampPosMax_EC | percent (98) | x | x | x | x | x | x | RD |
27 | DampPosMin_EC | percent (98) | x | x | x | x | x | x | RD |
28 | DampPosMax_SC | percent (98) | x | x | x | x | x | x | RD |
29 | DampPosMin_SC | percent (98) | x | x | x | x | x | x | RD |
30 | DampPosMax_TS | percent (98) | x | x | x | x | x | x | RD |
31 | DampPosMin_TS | percent (98) | x | x | x | x | x | x | RD |
32 | VolflowSet_R | l/s (87) | WR, RD | ||||||
33 | PressSet | pascal (57) | WR, RD | ||||||
34 | Volt_AI2 | volt (5) | x | x | x | x | x | x | RD |
35 | Volt_AI3 | volt (5) | x | x | x | x | x | x | RD |
36 | Volt_AO2 | volt (5) | x | x | x | x | x | x | WR, RD |
FH: Fume cupboard controller
RR: Room controller for supply air or extract air (RS, RE, PC)
RR RMF: Room controller with active room management function
EC, SC: Single controller for supply air or extract air (EC, SC)
TAM: Adapter module
TAM RMF: Adapter module with active room management function
Binary Value Objects
1 | LocalAlarm (COVU) | x | x | x | x | x | x | RD |
2 | SummaryAlarm (COVU) | x | x | RD | ||||
3 | PressAlarm (COVU) | x | x | RD | ||||
4 | ManOP_Disable | x1 | x | x | WR, RD | |||
5 | PressSetSel | x | x | WR, RD | ||||
6 | DI1 | x | x | x | x | x | x | RD |
7 | DI2 | x | x | x | x | x | x | RD |
8 | DI3 | x | x | x | x | x | x | RD |
9 | DI4 | x | x | x | x | x | x | RD |
10 | DI5 | x | x | x | x | x | x | RD |
11 | DI6 | x | x | x | x | x | x | RD |
12 | DO1 | x | x | x | x | x | x | RD |
13 | DO2 | x | x | x | x | x | x | RD |
14 | DO3 | x | x | x | x | x | x | RD |
15 | DO4 | x | x | x | x | x | x | RD |
16 | DO5 | x | x | x | x | x | x | RD |
17 | DO6 | x | x | x | x | x | x | RD |
18 | SC_Alarm | RD | ||||||
19 | DO1_Set | x | x | x | x | x | x | WR, RD |
20 | DO2_Set | x | x | x | x | x | x | WR, RD |
21 | DO3_Set | x | x | x | x | x | x | WR, RD |
22 | DO4_Set | x | x | x | x | x | x | WR, RD |
23 | DO5_Set | x | x | x | x | x | x | WR, RD |
24 | DO6_Set | x | x | x | x | x | x | WR, RD |
25 | DO1_SetByLocal | x | x | x | x | x | x | RD |
26 | DO2_SetByLocal | x | x | x | x | x | x | RD |
27 | DO3_SetByLocal | x | x | x | x | x | x | RD |
28 | DO4_SetByLocal | x | x | x | x | x | x | RD |
29 | DO5_SetByLocal | x | x | x | x | x | x | RD |
30 | DO6_SetByLocal | x | x | x | x | x | x | RD |
1 only for individually selected operating mode (stand-alone operation)
FH: Fume cupboard controller
RR: Room controller for supply air or extract air (RS, RE, PC)
RR RMF: Room controller with active room management function
EC, SC: Single controller for supply air or extract air (EC, SC)
TAM: Adapter module
TAM RMF: Adapter module with active room management function
Modbus interface
Application
The expansion module EM-BAC-MOD supports the following interface functions on an EASYLAB controller TCU3 or an adapter module TAM if the Modbus protocol has been selected:
Modbus functions
1 (0x01) | Read Coils | Read states of 1 to 8 bits according to bit list |
3 (0x03) | Read Holding Registers | Read several consecutive registers |
4 (0x04) | Read Input Registers | Read several consecutive registers |
5 (0x05) | Write Single Coil | Write state of a single bit |
6 (0x06) | Write Single Register | Write single register |
8 (0x08) | Diagnostics | Check Modbus communication |
16 (0x10) | Write Multiple Registers | Write several consecutive registers |
43 (0x2B) | Read Device Identification | Read identification data for the device |
14 (0x0E) | Read Device Identification | Read identification data for the device |
Exception codes
1 | Illegal Function Code | Unknown function or subfunction code |
2 | Illegal Data Address | Invalid register address |
3 | Illegal Data Value | Inconsistent coding for number of registers/bytes, data value |
Exception codes (error codes) are returned in case of invalid function or register access.
Bit list for ReadCoil/WriteSingleCoil functions
0 | ManOP_Disable | x1 | x | x | WR | |||
1 | PressSetSel | x | x | WR | ||||
2 | Local Alarm | x | x | x | x | x | x | RD |
3 | SummaryAlarm | x | x | RD | ||||
4 | PressAlarm | x | x | RD | ||||
5 | SC_SetlockHighPrio | WR | ||||||
6 | SC_GetLockHighPrio | RD | ||||||
7 | SC_Alarm | RD |
1 only for individually selected operating mode (stand-alone operation)
Bits are read with function 1 (RD) or written with function 5 (WR).
FH: Fume cupboard controller
RR: Room controller for supply air or extract air (RS, RE, PC)
RR RMF: Room controller with active room management function
EC, SC: Single controller for supply air or extract air (EC, SC)
TAM: Adapter module
TAM RMF: Adapter module with active room management function
Register list for Read***Registers and Write***Registers functions
0 | Mode | x1 |
| x | x | WR | ||
1 | ManOP_Disable | x1 |
| x | x | WR | ||
2 | ModeAct | x | x | x | x | RD | ||
3 | VolflowAct | x | x | x | x | RD | ||
4 | VolflowSet | x | x | x | x | RD | ||
5 | VelocityAct | x |
| RD | ||||
6 | VelocitySet | x |
| RD | ||||
7 | VolTotalExh | x | x | x | x | x | x | RD |
8 | VolTotalSup | x | x | x | x | x | x | RD |
9 | VolOffset_T |
|
| x | x | WR | ||
10 | VolOffset_P |
|
| x | x | WR | ||
11 | PressAct |
|
| x | x | RD | ||
12 | PressSet |
|
| x | x | RD | ||
13 | PressSetSel |
|
| x | x | WR | ||
14 | DampPos | x | x | x | x | RD | ||
15 | DampPosMax_FH - Value | x | x | x | x | x | x | RD |
16 | DampPosMax_FH - Status | x | x | x | x | x | x | RD |
17 | DampPosMin_FH - Value | x | x | x | x | x | x | RD |
18 | DampPosMin_FH - Status | x | x | x | x | x | x | RD |
19 | DampPosMax_RE - Value | x | x | x | x | x | x | RD |
20 | DampPosMax_RE - Status | x | x | x | x | x | x | RD |
21 | DampPosMin_RE - Value | x | x | x | x | x | x | RD |
22 | DampPosMin_RE - Status | x | x | x | x | x | x | RD |
23 | DampPosMax_TE - Value | x | x | x | x | x | x | RD |
24 | DampPosMax_TE - Status | x | x | x | x | x | x | RD |
25 | DampPosMin_TE - Value | x | x | x | x | x | x | RD |
26 | DampPosMin_TE - Status | x | x | x | x | x | x | RD |
27 | DampPosMax_RS - Value | x | x | x | x | x | x | RD |
28 | DampPosMax_RS - Status | x | x | x | x | x | x | RD |
29 | DampPosMin_RS - Value | x | x | x | x | x | x | RD |
30 | DampPosMin_RS - Status | x | x | x | x | x | x | RD |
31 | LocalAlarm | x | x | x | x | x | x | RD |
32 | SummaryAlarm |
|
| x | x | RD | ||
33 | PressAlarm |
|
| x | x | RD | ||
34 | WireSensorPos | x |
| RD | ||||
35 | SwitchPos | x |
| RD | ||||
36 | RoomModeAct |
|
| x | x | RD | ||
37 | SystemDevices | x | x | x | x | x | x | RD |
38 | SunBlind |
|
| x | x | WR | ||
39 | StateDI | x | x | x | x | x | x | RD |
40 | StateDO | x | x | x | x | x | x | RD |
41 | VolflowExh | x | x | x | x | x | WR | |
42 | VolflowSup | x | x | x | x | x | WR | |
43 | SC_SetLockHighPrio | WR | ||||||
44 | SC_GetLockHighPrio | RD | ||||||
45 | SC_SetPos - Value | WR | ||||||
46 | SC_SetPos - Status | WR | ||||||
47 | SC_GetPos | RD | ||||||
48 | SC_Alarm | RD | ||||||
49 | DampPosMax_EC - Value | x | x | x | x | x | x | RD |
50 | DampPosMax_EC - Status | x | x | x | x | x | x | RD |
51 | DampPosMin_EC - Value | x | x | x | x | x | x | RD |
52 | DampPosMin_EC - Status | x | x | x | x | x | x | RD |
53 | DampPosMax_SC - Value | x | x | x | x | x | x | RD |
54 | DampPosMax_SC - Status | x | x | x | x | x | x | RD |
55 | DampPosMin_SC - Value | x | x | x | x | x | x | RD |
56 | DampPosMin_SC - Status | x | x | x | x | x | x | RD |
57 | DampPosMax_TS - Value | x | x | x | x | x | x | RD |
58 | DampPosMax_TS - Status | x | x | x | x | x | x | RD |
59 | DampPosMin_TS - Value | x | x | x | x | x | x | RD |
60 | DampPosMin_TS - Status | x | x | x | x | x | x | RD |
61 | DO_Set | x | x | x | x | x | x | WR |
62 | DO_SetByLocal | x | x | x | x | x | x | RD |
63 | VolflowSet_R | WR, RD | ||||||
64 | PressSet | WR, RD | ||||||
65 | Volt_AI2 | x | x | x | x | x | x | RD |
66 | Volt_AI3 | x | x | x | x | x | x | RD |
67 | Volt_AO2 | x | x | x | x | x | x | WR, RD |
1 only for individually selected operating mode (stand-alone operation)
FH: Fume cupboard controller
RR: Room controller for supply air or extract air (RS, RE, PC)
RR RMF: Room controller with active room management function
EC, SC: Single controller for supply air or extract air (EC, SC)
TAM: Adapter module
TAM RMF: Adapter module with active room management function
Data points – detailed description
The following is a detailed description of the information that each data point provides; input variables and output variables are described separately:
Installation and commissioning
Installation
Commissioning
Condividi pagina
Consiglia questa pagina
Consiglia questa pagina inviando un link via e-mail.
Condividi pagina
Grazie per la tua condivisione!
La tua segnalazione è stata inviata e dovrebbe arrivare a breve.
Contatti
Siamo qui per te
Specifichi il suo messaggio ed il tipo di richiesta
Tel.: +41 26 425 59 00 | Fax: +41 55 250 73 10 | Fax Fribourg: +41 26 425 59 01
Contatti
Grazie per il tuo messaggio!
Il tuo messaggio è stato inviato e sarà processato a breve.
Il nostro dipartimento per la gestione delle richieste ti contatterà appena possibile.
Per domande di carattere generale riguardanti i nostri prodotti o servizi, è possibile contattare:
Tel.: +41 26 425 59 00 | Fax: +41 55 250 73 10 | Fax Fribourg: +41 26 425 59 01
Contatti
Siamo qui per te
Specifichi il suo messaggio ed il tipo di richiesta
Tel.: +41 26 425 59 00 | Fax: +41 55 250 73 10 | Fax Fribourg: +41 26 425 59 01
Contatti
Grazie per il tuo messaggio!
Il tuo messaggio è stato inviato e sarà processato a breve.
Il nostro dipartimento per la gestione delle richieste ti contatterà appena possibile.
Per domande di carattere generale riguardanti i nostri prodotti o servizi, è possibile contattare:
Tel.: +41 26 425 59 00 | Fax: +41 55 250 73 10 | Fax Fribourg: +41 26 425 59 01