00131950_0
Actuator LM24A


00131950_0

OPEN/CLOSE ACTUATORS 

For the opening and closing of shut-off dampers in air conditioning systems

Actuators for Type AK or AKK shut-off dampers

  • Change of the damper blade position for two different operating situations
  • Supply voltage 24 V AC/DC or 230 V AC or operating pressure 1 bar
  • Control input signal: 1-wire control or 2-wire control (3-point)
  • Mechanical stops
  • Retrofit possible

Application

Application

  • Actuators for opening and closing
  • Opening and closing of Type AK or AKK shut-off dampers

Description

Parts and characteristics

  • Mechanical stops for setting the damper blade positions
  • Electric or pneumatic operation
  • Overload protection
  • Control input signal: 1-wire control, 2-wire control (3-point) or pneumatic control
  • Optional spring return actuator for damper blade safety function
  • Optional auxiliary switch for capturing the end positions

Technical information

Function, Technical data, Produktbeziehungen

  • Function
  • Technical data

Functional description

The actuator opens or closes the damper blade.

Minimum and maximum positions can be set using mechanical stops.

1-wire control or 2-wire control (3-point) can be used.

1-wire control is actually an open/close control.


A spring return actuator moves the damper blade to the safe position in case of a power failure. Define the safe position with the order code: NC (normally closed) or NO (normally open). The spring return actuator is factory set according to the safe position.

The normal position of the damper blade is only achieved with 1-wire control (control voltage).

Control options and effect of actuator action in case of factory setting

Order code detail Function Control Direction of rotation
Order code detail Function Control 1 2

B30, B32

Open/close

1-wire control, 2-wire control

CLOSED

OPEN

B40, B42

Open/close

1-wire control, 2-wire control

CLOSED

OPEN

BP0, BP2

Open/close

1-wire control (spring return)



BR0, BR2

Open/close

1-wire control (spring return)




Actuators LM24A and LM24A-F

Supply voltage (AC)

24 V AC ± 20 %, 50/60 Hz

Supply voltage (DC)

24 V DC ± 20 %

Power consumption – load

1 W

Power consumption – idle

0.2 W

Power rating

1.5 VA

Torque

5 Nm

Running time for 90°

150 s

Control input signal

1-wire control or 2-wire control (3-point)

Connecting cable

3 × 0.75 mm², 1 m long

IEC protection class

III (protective extra-low voltage)

Protection level

IP 54

EC conformity

EMC to 2014/30/EU, RoHS to 2011/65/EU

Operating temperature

–30 to 50 °C

Weight

0.5 kg


Actuator LM230A and LM230A-F

Supply voltage

100 – 240 V AC –15 % +10 %, 50/60 Hz

Power consumption – load

1.5 W

Power consumption – idle

0.5 W

Power rating

3.5 VA

Torque

5 Nm

Running time for 90°

150 s

Control input signal

1-wire control or 2-wire control (3-point)

Connecting cable

3 × 0.75 mm², 1 m long

IEC protection class

II (protective insulation)

Protection level

IP 54

EC conformity

EMC to 2014/30/EU, low voltage to 2014/35/EU, RoHS to 2011/65/EU

Operating temperature

–30 to 50 °C

Weight

0.5 kg


Auxiliary switch S2A

Type of contact

2 changeover contacts1)

Max. switching voltage (AC)

250 V AC

Max. switching current (AC)

3 A (resistive load); 0.5 A (inductive load)

Max. switching voltage (DC)

110 V DC

Max. switching current (DC)

0.5 A (resistive load); 0.2 A (inductive load)

Connecting cable

6 × 0.75 mm², 1 m long

IEC protection class

II (protective insulation)

Protection level

IP 54

EC conformity

EMC to 2014/30/EU, low voltage to 2014/35/EU, RoHS to 2011/65/EU

Operating temperature

–30 to 50 °C

Weight

0.250 kg

1) If both auxiliary switches are used the switching voltages must be the same


Spring return actuator NF24A

Supply voltage (AC)

24 V AC ± 20 %, 50/60 Hz

Supply voltage (DC)

24 V DC –10 %, +20 %

Power consumption – load

6 W

Power consumption – idle

2.5 W

Power rating

8.5 VA

Torque

10 Nm

Motor running time for 90°

< 75 s

Spring return time

20 s (for < −20 °C up to 60 s)

Control input signal

Supply voltage on/off

Connecting cable

2 × 0.75 mm², 1 m long

IEC protection class

III (protective extra-low voltage)

Protection level

IP 54

EC conformity

EMC to 2014/30/EU, RoHS to 2011/65/EU

Operating temperature

–30 to 50 °C

Weight

1.8 kg


Spring return actuator NF24A-S2

Supply voltage (AC)

24 V AC ± 20 %, 50/60 Hz

Supply voltage (DC)

24 V DC –10 %, +20 %

Power consumption – load

6 W

Power consumption – idle

2.5 W

Power rating

8.5 VA

Torque

10 Nm

Motor running time for 90°

< 75 s

Spring return time

20 s (for < −20 °C up to 60 s)

Control input signal

Supply voltage on/off

Auxiliary switch: type of contact

2 changeover contacts1)

Max. switching voltage (AC)

250 V AC

Max. switching current (AC)

3 A (resistive load); 0.5 A (inductive load)

Max. switching voltage (DC)

110 V DC

Max. switching current (DC)

0.5 A (resistive load); 0.2 A (inductive load)

Connecting cable – actuator

2 × 0.75 mm², 1 m long

Connecting cable – auxiliary switch

6 × 0.75 mm², 1 m long

IEC protection class

III (protective extra-low voltage)

Protection level

IP 54

EC conformity

EMC to 2014/30/EU, RoHS to 2011/65/EU

Operating temperature

–30 to 50 °C

Weight

2.0 kg

1) If both auxiliary switches are used the switching voltages must be the same


Spring return actuator NFA

Supply voltage (AC)

24 – 240 V AC –20 % +10 %, 50/60 Hz

Supply voltage (DC)

24 – 125 V DC ±10 %

Power consumption – load

6 W

Power consumption – idle

2.5 W

Power rating

9.5 VA

Torque

10 Nm

Motor running time for 90°

< 75 s

Spring return time

20 s (for < −20 °C up to 60 s)

Control input signal

Supply voltage on/off

Connecting cable

2 × 0.75 mm², 1 m long

IEC protection class

II (protective insulation)

Protection level

IP 54

EC conformity

EMC to 2014/30/EU, low voltage to 2014/35/EU, RoHS to 2011/65/EU

Operating temperature

–30 to 50 °C

Weight

2.0 kg


Spring return actuator NFA-S2

Supply voltage (AC)

24 – 240 V AC –20 % +10 %, 50/60 Hz

Supply voltage (DC)

24 – 125 V DC ±10 %

Power consumption – load

6 W

Power consumption – idle

2.5 W

Power rating

9.5 VA

Torque

10 Nm

Motor running time for 90°

< 75 s

Spring return time

20 s (for < −20 °C up to 60 s)

Control input signal

Supply voltage on/off

Auxiliary switch: type of contact

2 changeover contacts1)

Max. switching voltage (AC)

250 V AC

Max. switching current (AC)

3 A (resistive load); 0.5 A (inductive load)

Max. switching voltage (DC)

110 V DC

Max. switching current (DC)

0.5 A (resistive load); 0.2 A (inductive load)

Connecting cable – actuator

2 × 0.75 mm², 1 m long

Connecting cable – auxiliary switch

6 × 0.75 mm², 1 m long

IEC protection class

II (protective insulation)

Protection level

IP 54

EC conformity

EMC to 2014/30/EU, low voltage to 2014/35/EU, RoHS to 2011/65/EU

Operating temperature

–30 to 50 °C

Weight

2.2 kg

1) If both auxiliary switches are used the switching voltages must be the same


Pneumatic actuator B555DC2

Control pressure

0.2 – 1.0 bar

Maximum pressure

2.0 bar

Compressed air

Compressed air for instruments, free of oil, water and dust

Weight

0.840 kg


Variants

  • Variants

Any attachments are to be defined with the order code of the shut-off damper.

B3*

Application

  • Actuator LM24A
  • Opening and closing of Type AK or AKK shut-off dampers

Variants

  • B32: with auxiliary switch for capturing the end positions

Parts and characteristics

  • Supply voltage 24 V AC/DC
  • 1-wire control or 2-wire control (3-point)
  • Mechanical stops for setting the volume flow rate setpoints
  • Switch for setting the direction of rotation
  • Release button to allow for manual operation

Installation and commissioning

  • Change the direction of rotation if necessary, using the switch

B4*

Application

  • Actuator LM230A
  • Opening and closing of Type AK or AKK shut-off dampers

Variants

  • B42: with auxiliary switch for capturing the end positions

Parts and characteristics

  • Supply voltage 100 – 240 V AC
  • 1-wire control or 2-wire control (3-point)
  • Mechanical stops for setting the volume flow rate setpoints
  • Switch for setting the direction of rotation
  • Release button to allow for manual operation

Installation and commissioning

  • Change the direction of rotation if necessary, using the switch

B*2

Application

  • Auxiliary switch S2A for capturing damper blade end positions (end positions reached through actuator operation)
  • Volt-free contacts for signalling or activating switch functions
  • Two integral switches, e.g. for damper blade OPEN and damper blade CLOSED
  • Potentiometer for setting any switch point

BP0

Application

  • Pneumatic actuator NF24A for the opening and closing of Type AK or AKK shut-off dampers
  • Opening and closing with safety function
  • The safety function of the shut-off damper is defined with the order code

Parts and characteristics

  • Supply voltage 24 V AC/DC
  • Control input signal: Supply voltage on/off
  • Mechanical stops for setting the volume flow rate setpoints
  • Manual operation using crank handle and position lock

BP2

Application

  • Spring return actuator NF24A-S2 with integral auxiliary switches for the opening and closing of Type AK or AKK shut-off dampers
  • Opening and closing of shut-off dampers with safety function
  • The safety function of the shut-off damper is defined with the order code

Parts and characteristics

  • Supply voltage 24 V AC/DC
  • Control input signal: Supply voltage on/off
  • Mechanical stops for setting the volume flow rate setpoints
  • Manual operation using crank handle and position lock
  • One fixed and one adjustable auxiliary switch for signalling rotation angles of 10 % and 10 – 90 %.
  • Fixed auxiliary switch, switching point 10 %
  • Adjustable auxiliary switch, switching point 10 – 90 %

BR0

Application

  • Pneumatic actuator NFA for the opening and closing of Type AK or AKK shut-off dampers
  • Opening and closing with safety function
  • The safety function of the shut-off damper is defined with the order code

Parts and characteristics

  • Supply voltage 24 – 240 V AC/24 – 125 V DC
  • Control input signal: Supply voltage on/off
  • Mechanical stops for setting the volume flow rate setpoints
  • Manual operation using crank handle and position lock

BR2

Application

  • Spring return actuator NFA-S2 with integral auxiliary switches for the opening and closing of Type AK or AKK shut-off dampers
  • Opening and closing with safety function
  • The safety function of the shut-off damper is defined with the order code

Parts and characteristics

  • Supply voltage 24 – 240 V AC or 24 – 125 V DC
  • Control input signal: Supply voltage on/off
  • Mechanical stops for setting the volume flow rates
  • Manual operation using crank handle and position lock
  • Two auxiliary switches with volt-free contacts for signalling or activating switch functions
  • Fixed auxiliary switch, switching point 10 %
  • Adjustable auxiliary switch, switching point 10 – 90 %

TN0

Application

  • Pneumatic actuator B555DC2 for the opening and closing of Type AK or AKK shut-off dampers
  • Opening and closing with safety function
  • The safety function of the shut-off damper is defined with the order code

Parts and characteristics

  • Control pressure 0.2 – 1 bar
  • Control input signal: pneumatic, control pressure on/off
  • Piston rod with 85 mm stroke
  • When the control pressure increases, the piston rod extends; it retracts by means of the spring force

Actuators for Type AK or AKK shut-off dampers

Order code detail Actuator Auxiliary switch
Order code detail Part number Type Supply voltage Part number Type

B30

M466DU5

LM24A

24 V

B32

M466DU5

LM24A

24 V

M536AI3

S2A

B40

M466DU4

LM230A

230 V

B42

M466DU4

LM230A

230 V

M536AI3

S2A

BP0

M466ET0

NF24A spring return actuator

24 V

BP2

M466ET2

NF24A-S2 spring return actuator

24 V


integrated

BR0

M466ET1

NFA spring return actuator

24 – 240 V AC 24 – 125 V DC

BR2

M466ET3

NFA-S2 spring return actuator

24 – 240 V AC 24 – 125 V DC


integrated

TN0

B555DC2

Pneumatic control

0.2 – 1 bar



Electrical connection

  • Electrical connection

Downloads

informazioni di prodotto

production {"X-Frame-Options"=>"SAMEORIGIN", "X-XSS-Protection"=>"1; mode=block", "X-Content-Type-Options"=>"nosniff", "X-Download-Options"=>"noopen", "X-Permitted-Cross-Domain-Policies"=>"none", "Referrer-Policy"=>"strict-origin-when-cross-origin", "Strict-Transport-Security"=>"max-age=31536000; includeSubDomains", "Content-Type"=>"text/html; charset=utf-8"}

Condividi pagina

Consiglia questa pagina

Consiglia questa pagina inviando un link via e-mail.

I campi contrassegnati con (*) sono obbligatori.

Condividi pagina

Grazie per la tua condivisione!

La tua segnalazione è stata inviata e dovrebbe arrivare a breve.


Contatti

Siamo qui per te

Specifichi il suo messaggio ed il tipo di richiesta
Tel.: +41 26 425 59 00 | Fax: +41 55 250 73 10 | Fax Fribourg: +41 26 425 59 01

Attachment (max. 10MB)

I campi contrassegnati con (*) sono obbligatori.

Contatti

Grazie per il tuo messaggio!

Il tuo messaggio è stato inviato e sarà processato a breve.
Il nostro dipartimento per la gestione delle richieste ti contatterà appena possibile.
Per domande di carattere generale riguardanti i nostri prodotti o servizi, è possibile contattare:
Tel.: +41 26 425 59 00 | Fax: +41 55 250 73 10 | Fax Fribourg: +41 26 425 59 01

Contatti

Siamo qui per te

Specifichi il suo messaggio ed il tipo di richiesta
Tel.: +41 26 425 59 00 | Fax: +41 55 250 73 10 | Fax Fribourg: +41 26 425 59 01

Attachment (max. 10MB)

I campi contrassegnati con (*) sono obbligatori.

Contatti

Grazie per il tuo messaggio!

Il tuo messaggio è stato inviato e sarà processato a breve.
Il nostro dipartimento per la gestione delle richieste ti contatterà appena possibile.
Per domande di carattere generale riguardanti i nostri prodotti o servizi, è possibile contattare:
Tel.: +41 26 425 59 00 | Fax: +41 55 250 73 10 | Fax Fribourg: +41 26 425 59 01