Application
Parts and characteristics
Any attachments are to be defined with the order code of the multileaf damper.
Actuators for multileaf dampers
Z12 | M466DD6 | SM230A | – | – | 20 Nm | 100 – 240 V AC |
Z13 | M466DG3 | GM230A | – | – | 40 Nm | 100 – 240 V AC |
Z14 | M466DD5 | SM24A | – | – | 20 Nm | 24 V |
Z15 | M466DG1 | GM24A | – | – | 40 Nm | 24 V |
Z16 | M466DD6 | SM230A | M536AI3 | S2A | 20 Nm | 100 – 240 V AC |
Z17 | M466DG3 | GM230A | M536AI3 | S2A | 40 Nm | 100 – 240 V AC |
Z18 | M466DD5 | SM24A | M536AI3 | S2A | 20 Nm | 24 V |
Z19 | M466DG1 | GM24A | M536AI3 | S2A | 40 Nm | 24 V |
Z42 | M466DU4 | LM230A | – | – | 5 Nm | 100 – 240 V AC |
Z43 | M466EM8 | NM230A | – | – | 10 Nm | 100 – 240 V AC |
Z44 | M466DU5 | LM24A | – | – | 5 Nm | 24 V |
Z45 | M466EM9 | NM24A | – | – | 10 Nm | 24 V |
Z46 | M466DU4 | LM230A | M536AI3 | S2A | 5 Nm | 100 – 240 V AC |
Z47 | M466EM8 | NM230A | M536AI3 | S2A | 10 Nm | 100 – 240 V AC |
Z48 | M466DU5 | LM24A | M536AI3 | S2A | 5 Nm | 24 V |
Z49 | M466EM9 | NM24A | M536AI3 | S2A | 10 Nm | 24 V |
Fast-running actuators for multileaf dampers
ZS21 | M466EU4 | SMQ24A | – | – | 16 Nm | 24 V |
ZS22 | M466EU4 | SMQ24A | M536AI3 | S2A | 16 Nm | 24 V |
Application
Variants
Parts and characteristics
Actuator SM24A
Supply voltage (AC) | 24 V AC ± 20 %, 50/60 Hz |
Supply voltage (DC) | 24 V DC −10 %, +20 % |
Power rating (AC) | 6 VA max. |
Power rating (DC) | 4 W max. |
Torque | 20 Nm |
Running time for 90° | 150 s |
Control input signal | 1-wire control or 2-wire control (3-point) |
Connecting cable | 3 × 0.75 mm², 1 m long |
IEC protection class | III (protective extra-low voltage) |
Protection level | IP 54 |
EC conformity | EMC to 2014/30/EU, RoHS to 2011/65/EU |
Operating temperature | –30 to 50 °C |
Weight | 1.0 kg |
Actuator GM24A
Supply voltage (AC) | 24 V AC ± 20 %, 50/60 Hz |
Supply voltage (DC) | 24 V DC ± 20 % |
Power rating (AC) | 6 VA max. |
Power rating (DC) | 4 W max. |
Torque | 40 Nm |
Running time for 90° | 150 s |
Control input signal | 1-wire control or 2-wire control (open/close) |
Connecting cable | 3 × 0.75 mm², 1 m long |
IEC protection class | III (protective extra-low voltage) |
Protection level | IP 54 |
EC conformity | EMC to 2014/30/EU, RoHS to 2011/65/EU |
Operating temperature | –30 to 50 °C |
Weight | 1.7 kg |
Actuators LM24A and LM24A-F
Supply voltage (AC) | 24 V AC ± 20 %, 50/60 Hz |
Supply voltage (DC) | 24 V DC ± 20 % |
Power consumption – load | 1 W |
Power consumption – idle | 0.2 W |
Power rating | 1.5 VA |
Torque | 5 Nm |
Running time for 90° | 150 s |
Control input signal | 1-wire control or 2-wire control (3-point) |
Connecting cable | 3 × 0.75 mm², 1 m long |
IEC protection class | III (protective extra-low voltage) |
Protection level | IP 54 |
EC conformity | EMC to 2014/30/EU, RoHS to 2011/65/EU |
Operating temperature | –30 to 50 °C |
Weight | 0.5 kg |
Actuator NM24A
Supply voltage (AC) | 24 V AC ± 20 %, 50/60 Hz |
Supply voltage (DC) | 24 V DC ±20 % |
Power rating (AC) | 3.5 VA max. |
Power rating (DC) | 1.5 W max. |
Torque | 10 Nm |
Running time for 90° | 150 s |
Control input signal | 1-wire control or 2-wire control (3-point) |
Connecting cable | 3 × 0.75 mm², 1 m long |
IEC protection class | III (protective extra-low voltage) |
Protection level | IP 54 |
EC conformity | EMC to 2014/30/EU, RoHS to 2011/65/EU |
Operating temperature | –30 to 50 °C |
Weight | 0.75 kg |
Fast-running actuator SMQ24A
Supply voltage (AC) | 24 V AC ± 20 %, 50/60 Hz |
Supply voltage (DC) | 24 V DC −10 %, +20 % |
Power rating (AC) | 26 VA max. |
Power rating (DC) | 15 W max. |
Torque | 16 Nm |
Running time for 90° | 7 s |
Control input signal | 1-wire control |
Connecting cable | 3 × 0.75 mm², 1 m long |
IEC protection class | III (protective extra-low voltage) |
Protection level | IP 54 |
EC conformity | EMC to 2014/30/EU, RoHS to 2011/65/EU |
Operating temperature | –30 to 40 °C |
Weight | 1.7 kg |
Application
Variants
Parts and characteristics
Actuator SM230A
Supply voltage | 100 – 240 V AC –15 % +10 %, 50/60 Hz |
Power rating | 6 VA max. |
Torque | 20 Nm |
Running time for 90° | 150 s |
Control input signal | 1-wire control or 2-wire control (3-point) |
Connecting cable | 3 × 0.75 mm², 1 m long |
IEC protection class | II (protective insulation) |
Protection level | IP 54 |
EC conformity | EMC to 2014/30/EU, low voltage to 2014/35/EU, RoHS to 2011/65/EU |
Operating temperature | –30 to 50 °C |
Weight | 1.0 kg |
Actuator GM230A
Supply voltage | 100 – 240 V AC –15 % +10 %, 50/60 Hz |
Power rating | 9 VA max. |
Torque | 40 Nm |
Running time for 90° | 150 s |
Control input signal | 1-wire control or 2-wire control (open/close) |
Connecting cable | 3 × 0.75 mm², 1 m long |
IEC protection class | II (protective insulation) |
Protection level | IP 54 |
EC conformity | EMC to 2014/30/EU, low voltage to 2014/35/EU, RoHS to 2011/65/EU |
Operating temperature | –30 to 50 °C |
Weight | 1.7 kg |
Actuator LM230A and LM230A-F
Supply voltage | 100 – 240 V AC –15 % +10 %, 50/60 Hz |
Power consumption – load | 1.5 W |
Power consumption – idle | 0.5 W |
Power rating | 3.5 VA |
Torque | 5 Nm |
Running time for 90° | 150 s |
Control input signal | 1-wire control or 2-wire control (3-point) |
Connecting cable | 3 × 0.75 mm², 1 m long |
IEC protection class | II (protective insulation) |
Protection level | IP 54 |
EC conformity | EMC to 2014/30/EU, low voltage to 2014/35/EU, RoHS to 2011/65/EU |
Operating temperature | –30 to 50 °C |
Weight | 0.5 kg |
Actuator NM230A
Supply voltage | 100 – 240 V AC –15 % +10 %, 50/60 Hz |
Power rating | 5.5 VA max. |
Torque | 10 Nm |
Running time for 90° | 150 s |
Control input signal | 1-wire control or 2-wire control (3-point) |
Connecting cable | 3 × 0.75 mm², 1 m long |
IEC protection class | II (protective insulation) |
Protection level | IP 54 |
EC conformity | EMC to 2014/30/EU, low voltage to 2014/35/EU, RoHS to 2011/65/EU |
Operating temperature | –30 to 50 °C |
Weight | 0.75 kg |
Application
Auxiliary switch S2A
Type of contact | 2 changeover contacts1) |
Max. switching voltage (AC) | 250 V AC |
Max. switching current (AC) | 3 A (resistive load); 0.5 A (inductive load) |
Max. switching voltage (DC) | 110 V DC |
Max. switching current (DC) | 0.5 A (resistive load); 0.2 A (inductive load) |
Connecting cable | 6 × 0.75 mm², 1 m long |
IEC protection class | II (protective insulation) |
Protection level | IP 54 |
EC conformity | EMC to 2014/30/EU, low voltage to 2014/35/EU, RoHS to 2011/65/EU |
Operating temperature | –30 to 50 °C |
Weight | 0.250 kg |
1) If both auxiliary switches are used the switching voltages must be the same
Condividi pagina
Consiglia questa pagina
Consiglia questa pagina inviando un link via e-mail.
Condividi pagina
Grazie per la tua condivisione!
La tua segnalazione è stata inviata e dovrebbe arrivare a breve.
Contatti
Siamo qui per te
Specifichi il suo messaggio ed il tipo di richiesta
Tel.: +41 26 425 59 00 | Fax: +41 55 250 73 10 | Fax Fribourg: +41 26 425 59 01
Contatti
Grazie per il tuo messaggio!
Il tuo messaggio è stato inviato e sarà processato a breve.
Il nostro dipartimento per la gestione delle richieste ti contatterà appena possibile.
Per domande di carattere generale riguardanti i nostri prodotti o servizi, è possibile contattare:
Tel.: +41 26 425 59 00 | Fax: +41 55 250 73 10 | Fax Fribourg: +41 26 425 59 01
Contatti
Siamo qui per te
Specifichi il suo messaggio ed il tipo di richiesta
Tel.: +41 26 425 59 00 | Fax: +41 55 250 73 10 | Fax Fribourg: +41 26 425 59 01
Contatti
Grazie per il tuo messaggio!
Il tuo messaggio è stato inviato e sarà processato a breve.
Il nostro dipartimento per la gestione delle richieste ti contatterà appena possibile.
Per domande di carattere generale riguardanti i nostri prodotti o servizi, è possibile contattare:
Tel.: +41 26 425 59 00 | Fax: +41 55 250 73 10 | Fax Fribourg: +41 26 425 59 01