Multileaf damper with actuator
Application
Special features
Classification
Air leakage with closed multileaf damper according to EN 1751: test pressure up to 2000 Pa
Nominal sizes
Parts and characteristics
Attachments
Accessories
Installation subframes for the fast and simple installation of multileaf dampers
Construction features
Materials and surfaces
Standards and guidelines
Closed multileaf damper air leakage to EN 1751, class 4
Maintenance
Multileaf dampers with gears can only have opposed action blades.
The internal gears transfer the synchronous rotational movement from the drive arm to the individual blades.
The torque for closing a multileaf damper must be dimensioned so that the damper can be safely opened and closed. For closure, the torque must suffice to ensure complete shut-off by the blades. Opening is initiated without aerodynamic forces. When air flows through the damper, the aerodynamic forces of the airflow create a closing force (torque) on the blades; this happens independently of the direction of the airflow. This closing force must be countered, or overcome. The blade angle α with the largest torque depends, among other things, on the fan characteristics.
Nominal sizes | 200 × 100 mm – 1200 × 1000 mm |
Maximum permitted static differential pressure for a closed multileaf damper | 2000 Pa |
Operating temperature | 0 to 60 °C |
Minimum torques [Nm]
H | B | |||||||||
---|---|---|---|---|---|---|---|---|---|---|
200 | 400 | 500 | 600 | 700 | 800 | 900 | 1000 | 1100 | 1200 | |
100 – 650 | 10 | 10 | 10 | 10 | 10 | 10 | 10 | 10 | 10 | 10 |
700 – 1000 | 20 | 20 | 20 | 20 | 20 | 20 | 20 | 20 | 20 | 20 |
Free cross-sectional area [m²]
H | B | ||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
200 | 300 | 400 | 500 | 600 | 700 | 800 | 900 | 1000 | 1100 | 1200 | |
100, 150 | 0.014 | 0.022 | 0.03 | 0.038 | 0.047 | 0.055 | 0.063 | 0.071 | 0.079 | 0.087 | 0.095 |
200, 250 | 0.028 | 0.045 | 0.061 | 0.077 | 0.093 | 0.109 | 0.126 | 0.142 | 0.158 | 0.174 | 0.19 |
300, 350 | 0.043 | 0.067 | 0.091 | 0.115 | 0.14 | 0.164 | 0.188 | 0.213 | 0.237 | 0.261 | 0.286 |
400, 450 | 0.057 | 0.089 | 0.122 | 0.154 | 0.186 | 0.219 | 0.251 | 0.284 | 0.316 | 0.348 | 0.381 |
500, 550 | 0.071 | 0.111 | 0.152 | 0.192 | 0.233 | 0.273 | 0.314 | 0.354 | 0.395 | 0.435 | 0.476 |
600, 650 | 0.085 | 0.134 | 0.182 | 0.231 | 0.279 | 0.328 | 0.377 | 0.425 | 0.474 | 0.522 | 0.571 |
700, 750 | 0.099 | 0.156 | 0.213 | 0.269 | 0.326 | 0.383 | 0.439 | 0.496 | 0.553 | 0.61 | 0.666 |
800, 850 | 0.113 | 0.178 | 0.243 | 0.308 | 0.373 | 0.437 | 0.502 | 0.567 | 0.632 | 0.697 | 0.761 |
900, 950 | 0.128 | 0.2 | 0.273 | 0.346 | 0.419 | 0.492 | 0.565 | 0.638 | 0.711 | 0.784 | 0.857 |
1000 | 0.142 | 0.223 | 0.304 | 0.385 | 0.466 | 0.547 | 0.628 | 0.709 | 0.79 | 0.871 | 0.952 |
Intermediate sizes: Interpolate values between widths.
Sound power level for a closed multileaf damper LWA [dB(A)]
Δpt [Pa] | Area B × H [m²] | ||||||||
---|---|---|---|---|---|---|---|---|---|
0.04 | 0.09 | 0.16 | 0.25 | 0.36 | 0.64 | 0.81 | 1 | 1.2 | |
100 | <10 | <10 | <10 | <10 | 10 | 12 | 13 | 14 | 15 |
200 | <10 | 14 | 16 | 17 | 19 | 22 | 22 | 23 | 25 |
500 | 22 | 26 | 28 | 30 | 32 | 34 | 35 | 36 | 37 |
1000 | 32 | 35 | 37 | 39 | 41 | 43 | 44 | 45 | 46 |
1500 | 37 | 41 | 43 | 44 | 46 | 49 | 50 | 51 | 52 |
2000 | 41 | 44 | 47 | 49 | 51 | 53 | 54 | 55 | 56 |
Quick sizing tables provide a good overview of the sound power levels and differential pressures that can be expected. Approximate intermediate values can be interpolated. Precise intermediate values and spectral data can be calculated with our Easy Product Finder design program. The sound power levels LWA apply to multileaf dampers with a cross-sectional area (B × H) of 1 m². The differential pressures apply to multileaf dampers installed in ducts (installation type A).
Rectangular multileaf dampers for volume flow and pressure control as well as for low-leakage shut-off of ducts and openings in walls and ceiling slabs. Ready-to-operate unit which consists of the casing, aerofoil blades and the blade mechanism. Flanges on both sides, suitable for duct connection. The blade position is indicated externally by a notch in the blade shaft extension. Closed multileaf damper air leakage according to EN 1751, Class 4. Casing leakage according to EN 1751, Class C.
Special features
Materials and surfaces
Technical data
Sizing data
Air-regenerated noise
JZ-LL-AL | / | 1200 × 800 | / | ER | / | Z64 | / | NO | / | P1 – RAL … |
| | | | | | | | | | | | |||||
1 | 2 | 3 | 4 | 5 | 6 | |||||
Nominal size | 800 × 500 mm |
Installation subframe | None |
Attachments | Hold open device |
User interface | Anodised, EURAS E6-C-0, natural colour |
Quadrant stays and limit switches
Order code detail | Description | Limit switch | Function |
---|---|---|---|
Z04 | Hold open device | – | |
Z05 | Hold open device | 1 | Damper blade position CLOSED |
Z06 | Hold open device | 1 | Damper blade position OPEN |
Z07 | Hold open device | 2 | Damper blade positions CLOSED and OPEN |
Open/close actuators
Order code detail | Description | Function | Supply voltage | Torque | Auxiliary switch |
---|---|---|---|---|---|
Z12 | SM230A | 1-wire-control 2-wire-control (3-point) | 100 – 240 V AC | 20 Nm | – |
Z14 | SM24A | 1-wire-control 2-wire-control (3-point) | 24 V AC/DC | 20 Nm | – |
Z16 | SM230A | 1-wire-control 2-wire-control (3-point) | 100 – 240 V AC | 20 Nm | S2A |
Z18 | SM24A | 1-wire-control 2-wire-control (3-point) | 24 V AC/DC | 20 Nm | S2A |
Z43 | NM230A | 1-wire-control 2-wire-control (3-point) | 100 – 240 V AC | 10 Nm | – |
Z45 | NM24A | 1-wire-control 2-wire-control (3-point) | 24 V AC/DC | 10 Nm | – |
Z47 | NM230A | 1-wire-control 2-wire-control (3-point) | 100 – 240 V AC | 10 Nm | S2A |
Z49 | NM24A | 1-wire-control 2-wire-control (3-point) | 24 V AC/DC | 10 Nm | S2A |
Minimum torque of multileaf damper has to be considered when selecting the actuator
accordingly.
Open/close actuators, fast-running
Order code detail | Description | Function | Supply voltage | Torque | Auxiliary switch |
---|---|---|---|---|---|
ZS21 | SMQ24A | 1-wire-control | 24 V AC/DC | 16 Nm | – |
ZS22 | SMQ24A | 1-wire-control | 24 V AC/DC | 16 Nm | S2A |
Only up to height H ≤ 650 mm
Open/close actuators, spring return
Order code detail | Description | Function | Supply voltage | Torque | Auxiliary switch |
---|---|---|---|---|---|
ZF01 | NF24A | Supply voltage on/off | 24 V AC/DC | 10 Nm | – |
ZF02 | NFA | Supply voltage on/off | 24 – 240 V AC 24 – 125 V DC | 10 Nm | – |
ZF03 | NF24A-S2 | Supply voltage on/off | 24 V AC/DC | 10 Nm | integrated |
ZF04 | NFA-S2 | Supply voltage on/off | 24 – 240 V AC 24 – 125 V DC | 10 Nm | integrated |
ZF06 | SF24A | Supply voltage on/off | 24 V AC/DC | 20 Nm | – |
ZF07 | SFA | Supply voltage on/off | 24 – 240 V AC 24 – 125 V DC | 20 Nm | – |
ZF08 | SF24A-S2 | Supply voltage on/off | 24 V AC/DC | 20 Nm | integrated |
ZF09 | SFA-S2 | Supply voltage on/off | 24 – 240 V AC 24 – 125 V DC | 20 Nm | integrated |
ZF11 | EF24A | Supply voltage on/off | 24 V AC/DC | 30 Nm | – |
ZF12 | EF230A | Supply voltage on/off | 100 – 240 V AC | 30 Nm | – |
ZF13 | EF24A-S2 | Supply voltage on/off | 24 V AC/DC | 30 Nm | integrated |
ZF14 | EF230A-S2 | Supply voltage on/off | 100 – 240 V AC | 30 Nm | integrated |
Minimum torque of multileaf damper has to be considered when selecting the actuator.
Modulating actuators
Order code detail | Description | Function | Supply voltage | Torque | Auxiliary switch |
---|---|---|---|---|---|
Z20 | SM24A-SR | 2 – 10 V DC | 24 V AC/DC | 20 Nm | – |
Z21 | GM24A-SR | 2 – 10 V DC | 24 V AC/DC | 40 Nm | – |
Z51 | NM24A-SR | 2 – 10 V DC | 24 V AC/DC | 10 Nm | – |
Minimum torque of multileaf damper has to be considered when selecting the actuator.
Modulating actuators, spring return
Order code detail | Description | Function | Supply voltage | Torque | Auxiliary switch |
---|---|---|---|---|---|
ZF05 | NF24A-SR | 2 – 10 V DC | 24 V AC/DC | 10 Nm | – |
ZF10 | SF24A-SR | 2 – 10 V DC | 24 V AC/DC | 20 Nm | – |
ZF15 | EF24A-SR | 2 – 10 V DC | 24 V AC/DC | 30 Nm | – |
ZF05: Only up to height H ≤ 650
Double acting pneumatic actuators
Order code detail | Description | Damper blade safety function | Operating pressure | Torque at 6 bar | Limit switch | Solenoid valve |
---|---|---|---|---|---|---|
Z60 | DR030 | – | 1.2 – 6 bar | 35 Nm | – | |
Z61 | DR030 | power off to close/open | 1.2 – 6 bar | 35 Nm | – | 24 V DC |
Z62 | DR030 | power off to close/open | 1.2 – 6 bar | 35 Nm | – | 230 V AC |
Z63 | DR030 | – | 1.2 – 6 bar | 35 Nm | 2 | |
Z64 | DR030 | power off to close/open | 1.2 – 6 bar | 35 Nm | 2 | 24 V DC |
Z65 | DR030 | power off to close/open | 1.2 – 6 bar | 35 Nm | 2 | 230 V AC |
Z66 | DR060 | – | 1.2 – 6 bar | 70 Nm | – | |
Z67 | DR060 | power off to close/open | 1.2 – 6 bar | 70 Nm | – | 24 V DC |
Z68 | DR060 | power off to close/open | 1.2 – 6 bar | 70 Nm | – | 230 V AC |
Z69 | DR060 | – | 1.2 – 6 bar | 70 Nm | 2 | |
Z70 | DR060 | power off to close/open | 1.2 – 6 bar | 70 Nm | 2 | 24 V DC |
Z71 | DR060 | power off to close/open | 1.2 – 6 bar | 70 Nm | 2 | 230 V AC |
Minimum torque, which depends on the nominal size of multileaf damper, and the operating pressure have to be considered when selecting the actuator.
Single acting pneumatic actuators
Order code detail | Description | Damper blade safety function | Operating pressure | Limit switch | Torque at 6 bar | Solenoid valve |
---|---|---|---|---|---|---|
Z72 | SC060 SO060 | pressure off to close/open | 6 bar | 30 Nm | – | – |
Z73 | SC060 SO060 | power off and pressure off to close/open | 6 bar | 30 Nm | – | 24 V DC |
Z74 | SC060 SO060 | power off and pressure off to close/open | 6 bar | 30 Nm | – | 230 V AC |
Z75 | SC060 SO060 | pressure off to close/open | 6 bar | 30 Nm | 2 | – |
Z76 | SC060 SO060 | power off and pressure off to close/open | 6 bar | 30 Nm | 2 | 24 V DC |
Z77 | SC060 SO060 | power off and pressure off to close/open | 6 bar | 30 Nm | 2 | 230 V AC |
Partager la page
Recommander cette page
Vous avez la possibilité de recommander cette page en partageant le lien.
Contact
Merci pour votre message !
Votre recommandation a été envoyée et sera bientôt reçue par le destinataire.
Contact
Nous sommes à votre disposition
Veuillez préciser votre message et le type de demande.
Tel.: +41 26 425 59 00 | Fax: +41 26 425 59 01
Contact
Merci pour votre message !
Votre message a été envoyé et sera traité dans les plus brefs délais.
Notre département de traitement des demandes prendra contact avec vous dès que possible.
Pour les questions d'ordre général concernant les produits ou services, vous pouvez aussi nous appeler :
Tel.: +41 26 425 59 00 | Fax: +41 26 425 59 01
Contact
Nous sommes à votre disposition
Veuillez préciser votre message et le type de demande.
Tel.: +41 26 425 59 00 | Fax: +41 26 425 59 01
Contact
Merci pour votre message !
Votre message a été envoyé et sera traité dans les plus brefs délais.
Notre département de traitement des demandes prendra contact avec vous dès que possible.
Pour les questions d'ordre général concernant les produits ou services, vous pouvez aussi nous appeler :
Tel.: +41 26 425 59 00 | Fax: +41 26 425 59 01